0 comments

  1. Agreed. It is also evident that if the loss (energy) is not efficiently removed, it will cause degradation of the insulation. The transformer output may not be affected by this change but localised areas in the transformer may degrade at a faster rate due to the concentration of this \”loss energy\” resulting in eventual failure of the insulation and its properties.

  2. Thank you for reading my contribution to the body of knowledge on power transformers. Hopefully we can understand these aging/reliability mechanisms more clearly and make the correct decisions when designing and managing these very important assets.

  3. Hi Prince, thank you for the positive comments. Coopers Environmental provides a very important service to the industry. Maybe we can test your information out on the LEDT method.

  4. Hi Dilip, Thank you. If you have an interesting case study it would be great if we could test it out on the LEDT method and see if it could have given positive results in predicting the failure.

  5. Fantastic concise explanation on what is going on in the power transformer and more importantly the way forward.

  6. Insightful article. Are there means to manage/neutralise elevated CO and/or CO2 levels in a transformer until it can be taken out of service?

  7. […] ratio method utilizes the ratios of the concentration of the key gases Hydrogen H2, Methane CH4, Ethane C2H6, Ethylene C2H4, and Acetylene C2H2. The following ratios are used CH4/H2, C2H2/CH4, C2H4/C2H6, and […]

    • Thank you for your question.
      I would approach this in the following way:

      Example Calculation
      1. Rated Capacity of Transformer (S): 1000 kVA
      2. Temperature Rise Limit: Assume the maximum allowable temperature rise is 65°C above ambient temperature.
      3. Ambient Temperature (Ta): Assume ambient temperature is 30°C (use actuals)
      4. Temperature Rise with both fans (Assuming 2 fan cooling system): The transformer can operate at its rated capacity (1000 kVA) without exceeding the temperature rise limit.
      5. Cooling Efficiency Reduction: Assume the failure of one fan results in an increase in temperature rise by 20°C (this is an estimation; determine actual values).

      Step-by-Step Calculation:
      1. Calculate Maximum Operating Temperature (Tmax):
      Tmax = Ta + Temperature Rise Limit
      Tmax = 30°C + 65°C = 95°C

      2. Determine New Maximum Allowable Temperature with One Fan Failed:
      If one fan fails, the temperature rise limit increases by 20°C.
      Tmax new = Ta + (Temperature Rise Limit + 20°C)
      Tmax new = 30°C + (65°C + 20°C) = 30°C + 85°C = 115°C

      3. Calculate New Maximum Allowable Temperature Rise:
      New Temperature Rise Limit = Tmax new – Ta
      New Temperature Rise Limit = 115°C − 30°C = 85°C

      4. Calculate New Maximum Load Capacity:
      New Maximum Load Capacity = Rated Capacity × Load Capacity Ratio
      New Maximum Load Capacity = 1000 kVA × 65/85 ≈ 1000 kVA × 0.7647 ≈ 765 kVA

      Conclusion:
      With one cooling fan failed, the new maximum load capacity of the transformer is approximately 765 kVA. This is an example but you can use actuals values as per your scenario and onsite measurements.

  8. Rare to find transformer diagnostic tools shared this openly with the engineering community. The LEDT and TAIM work in particular is helping me shape a condition monitoring platform for our transmission fleet. Thanks for making this material available!!