Impedance (Load Loss) Test of a Power Transformer

The impedance (load loss) test is a diagnostic routine test that measures the power (watts) load losses in a transformer, which is usually expressed as an impedance voltage or percentage impedance.

This blog post delves into the purpose, methodology, and practical insights of the test to optimize transformer performance and ensure system reliability.

Load losses in a transformer occur due to the specified load it carries. These include I2R losses in the windings and stray losses from eddy currents in various conducting parts. Stray losses can also result from circulating currents in parallel windings. Load losses are measured by short-circuiting one winding and applying a voltage to the other to achieve the specified current. The resulting power loss represents the transformer’s load losses at the test temperature.


Purpose of the Impedance (Load Loss) Test

The primary objectives of the impedance (load loss) test are to:

  1. Determine Impedance Voltage: Verify the voltage drop caused by the impedance of the transformer.
  2. Measure Load Losses: Quantify the power losses occurring due to resistance and leakage reactance under load conditions.
  3. Ensure Design Compliance: Confirm that the impedance voltage and load loss values align with design specifications.
  4. Support Fault Analysis: Provide critical data for system fault level calculations and relay coordination.

Type of Test

The impedance (load loss) test is a routine test conducted in both factory and field environments as part of acceptance, type, and periodic maintenance testing. It is performed under controlled conditions to simulate operational load scenarios.


Problems Identified by the Test

This test can identify several potential issues, such as:

  • Excessive Losses: Highlights higher-than-expected load losses due to winding resistance or core inefficiencies.
  • Impedance Deviations: Detects deviations in impedance that may impact fault current levels and system stability.
  • Design Flaws: Reveals inconsistencies with design parameters that could affect transformer performance.
  • Manufacturing Defects: Identifies issues like improper winding arrangements or inadequate insulation.

Test Setup

Performing the impedance (load loss) test involves the following steps using the test circuit in Figure 1.

Figure 1: Test Circuit for Short Circuit Test
  1. Equipment Required:
    • AC Power source capable of delivering rated current.
    • Precision wattmeter (W), ammeter (A), and voltmeter (V).
    • Temperature measuring devices.
  2. Preparation:
    • De-energize and isolate the transformer from the system.
    • Ensure all terminals are securely connected.
    • Verify environmental conditions to standardize readings.
    • Apply short circuit to the low voltage terminals of the transformer
  3. Testing Procedure:
    • Apply rated current to the transformer’s primary winding.
    • Measure the voltage, current, and power loss on the secondary winding.
    • Record the impedance voltage and load loss values.

Passing Criteria and Tolerances

The test results should meet the following criteria:

  • Impedance Voltage: Should match the specified percentage on the transformer’s nameplate (e.g., 4% or 6%).
  • Load Losses: Should not exceed the manufacturer’s specified tolerances, typically within 5% of the design value.
  • Phase Balance: Impedance values between phases should remain consistent, with minimal variation.

International Standards

The impedance (load loss) test adheres to the following standards:

  • IEC 60076-1: Power Transformers—General Requirements.
  • IEEE C57.12.90: Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers.
  • IS 2026: Indian Standard for Power Transformers.

These standards specify test methodologies, equipment, and acceptable tolerances.


Key Points and Practical Experiences

  1. Temperature Correction: Correct load loss measurements to a standard temperature (e.g., 75°C) for consistency.
  2. Minimize Measurement Errors: Use calibrated instruments and ensure proper connections to avoid inaccuracies.
  3. Environmental Factors: Account for ambient conditions like temperature and humidity.
  4. Regular Testing: Conduct the test periodically to monitor transformer health and detect aging-related performance degradation.
  5. Skilled Personnel: Ensure the test is performed by experienced technicians to avoid errors and ensure safety.

Conclusion

The impedance (load loss) test is indispensable for verifying transformer performance and ensuring system reliability. By adhering to standardized procedures and maintaining accurate records, operators can proactively identify potential issues and optimize transformer operations, ensuring long-term efficiency and safety.

Leave a Reply